SEVEN-FMIC



Firefighter emergency microphone for public address and voice alarm system EN54 SEVEN

✓ Hand-held microphone for firefighter

✓ Emergency activation, alarm message playback and live alerts

✓ Intercom function with integrated speaker

HIGHLY RECOMMENDED IN

Description

Emergency microphone for public address system and voice alarm system EN54 SEVEN

  • The microphone allows firefighters or specialised personnel to activate emergencies, play alarm messages and give general warnings.
  • It is equipped with programmable buttons that can be assigned different functions. The number of buttons with extensions can be extended.
  • It makes it easy to deliver direct warnings to all areas.
  • Allows warnings to be issued even when the central control unit fails.
  • Performs operational monitoring at all times.
  • It has an intercom function and allows two-way communication between zone microphones.
SpecificationDescriptions
FEATURES:

Firefighter microphone PTT
Evacuation activation, alarm, alert messages and live warnings.
3 programmable buttons
Intercom function with integrated speaker.
LED operating indicator.
Interconnected by Cat5 network and SFP fibre.

BUTTONS:

Emergency activation button
3 programmable buttons, with the most frequent programming such as:
Evacuation
Alarm
Cancellation

SPEAKER:

2”
Power: 0.5 W
SPL: 78 dBA @1 W/1 m

MICROPHONE:

Response: 100-10,000 Hz
Sensitivity: -45 dB

INPUTS:

2 programmable GPI, Scart

OUTPUTS:

1 keyboard extension, RJ45
2 programmable GPO, Scart

PROTECTIONS:

IP31

TEMPERATURE:

Operation: -5ºC ~ 40ºC
Storage: -20ºC ~ 70ºC

HUMIDITY:

15% ~ 80% (non-condensing)

POWER SUPPLY:

DC 48 V, 15 W, POE or power adapter (not included), 266 mA

DIMENSIONS:

150 x 65 x 210 mm depth

WEIGHT:

1.5 kg